The situation
The homeowner wanted power at a remote corner of the property, about 100 feet past the house, for an RV and general outdoor use. A run that long needs a properly sized feeder in underground conduit, not an extension cord.
What we did
Ran SER cable from the main panel through the crawlspace under the house to an outdoor Cantex junction box
From there, trenched about 100 feet along the gravel driveway and laid 1-1/4" conduit underground
Pulled #2 conductors with a #6 ground for a 100A feeder
Installed an outdoor subpanel at the end of the run
Installed a [50A 14-50] RV receptacle and a 120V GFCI convenience outlet off the subpanel
Result
The homeowner now has a 100A subpanel at the far end of the property. The RV plugs into its own dedicated receptacle, there’s a GFCI outlet for tools and equipment, and the panel has room for future circuits.
Planning an RV hookup or outdoor subpanel? The main questions are the distance, the load and how much capacity your main panel can spare. We’ll run a load calculation and size the feeder for your run. Call (408) 661-0219.